
3
3.4 Heat Pump Sizing
Ensure that the correct size heat pump has been
selected in accordance with the latest version of
MIS3005 (for UK installation) and with the Dimplex
Heat Pump Planning Manual.
If a non A-Class heat pump cylinder is being used,
ensure that it has been accurately sized with the
appropriate coil surface area of the cylinder to
match the heat pump’s output and flow rate
requirements, and that all necessary hydraulic
connections have been considered in connecting it
to the heat pump system.
Ensure that suitable heat emitters have been sized
in accordance with the Heat Emitter Guide (for UK
installation) and selected ensuring a low flow
temperature design. To maximise system
efficiency it is important to design the system with
the lowest flow temperature possible.
3.5 Site Selection
3.5.1 Location of Heat Pump
The heat pump must be installed outdoors with
adequate clearances for ventilation and
maintenance. It is recommended that the heat
pump is installed along the property wall, as
shown in figure 4.
There must be a minimum distance of 1000mm in
front of the fan to prevent air re-circulation.
Positioning the heat pump in a confined space,
frost hollow or well will result in reduced heat
pump efficiency, as the cold air which is expelled
by the fan cannot disperse and may be drawn back
into the system. This means that the heat pump
may be operating using a lower inlet temperature
than what is actually available from the
thermostat, and will therefore run less efficiently.
The fan should preferably not face prevailing winds
to ensure correct air flow through the evaporator.
Although the heat pump is within noise and
vibration regulations outlined in MCS007, it is
recommended to avoid positioning it close to
bedroom windows, as the fan and compressor may
be operational at night.
3.5.2 Heat Pump Placement and Fixing
Approximately 2 litres of condensate water are
drained from the system every time a defrost cycle
occurs (approximately once every hour in colder
weather). Therefore, it is essential that the
condensate pipe is fed into a drain or soak away to
allow for safe disposal of the excess water, away
from footpaths or patios.
The condensate drain pipe is coiled up inside
the heat pump for protection during
transportation. In order to access this for
installation, the panels will need to be removed,
as shown in figure 9.
The length of the condensate pipe should be
kept to a minimum. This prevents parts of the
pipe from being exposed to the elements, which
could contribute to issues with freezing.
The removal of condensate must be secured
and the condensate pipe must be kept free
from debris and frost. Freezing of this pipe due
to incorrect installation can result in irreparable
damage and void warranty.
The condensate pipe should not run into sewer
pipe unless a suitable trap is installed, as fumes
may travel into the heat pump and cause
corrosion to the evaporator coil.
The heat pump must be fixed onto a level,
stable base that is capable of withstanding the
unit’s weight of 130kg, with a minimum of
50mm clearance around all sides of the heat
pump. It can be secured on the inside of the
heat pump with M10 anchor bolts, by removing
the outer panels and using the fixing holes
shown in figures 5.
The positions of the fixing holes can be located
by placing the heat pump on the plinth with the
condensate pipe aligned, and marking the
holes. Move or slide the heat pump to drill
holes.
Ideally the heat pump should be located close
to the property. Positioning of the heat pump at
a distance from the property will result in the
need for extra insulated pipe, which will lead to
extra cost, and result in additional heat losses.
Figure 4: Required free space around heat pump for
ventilation and maintenance
Comentários a estes Manuais