
5
Space Heating Only DHW with A-Class
Cylinder
Water Flow Rate
@ 2100 l/h (nominal) @ 1800 l/h (typical)
Associated Head Available
14 kPa 18kPa
Diameter (mm) Internal Diameter (mm) Maximum Equivalent Length (m)
~
22* 19.8 7 11
28^
25.6 23 38
32 29.6 46 77
Table 1: Maximum Equivalent Length for Copper Pipe
*Only suitable for special conditions ^Recommended pipe diameter
~
Assuming straight length with
no incidents (e.g. elbows, tees)
Isolation valves (non-return valve and ball
valve with strainer), supplied in the Dimplex
heat pump hydraulics pack, allow the strainer
to be removed and cleaned without having to
drain the system. Installation of these valves is
discussed in more detail in section 4.2.
If multiple heat emitter circuits are installed,
operating at different flow and return
temperatures (such as under floor heating and
standard radiators), a mixing valve must be
used to prevent high temperature water from
entering the under floor heating manifold.
Zone valves and pumps, if required, are sized
up by the installers to suit plumbing layout. A
suitable relay needs to be selected to energise
the pump.
EC pumps must not be connected directly to
the wiring centre because of high inrush
current. An auxiliary relay must be used.
Table 1 shows guidelines for the maximum length of
pipe allowed to achieve nominal flow rates, depending
on pipe diameter.
NOTE: Not all types of pipe will have the same
internal diameter, e.g. multi-layered/plastic pipes will
have a thicker wall so the guidelines set out in table 1
will not apply. Microbore (8mm) and 15mm pipe is
not suitable.
As a rule of thumb, the equivalent straight length (L
[mm]) of each elbow is found by multiplying the outer
diameter of the pipe (D [mm]) by 30, e.g. 4 elbows of
diameter 22mm pipe is equivalent to 2.5m of 22mm
pipe.
3.6.1 Buffer tank
The heat pump uses a reverse cycle defrost in order
to defrost the evaporator, which is an automated
process when required in cold/moist weather
conditions. Therefore, it is necessary to connect a
buffer tank in series with the heat pump, as shown in
the hydraulic schematic diagrams (Appendix B). The
Dimplex A-Class cylinder range come with an
integrated buffer tank, which;
Provides some energy storage for the unit to
carry out successful defrost.
Increases compressor life due to reduction in
the number of starts.
It is recommended that a buffer with a heating
element/immersion is used as it may be required if
initial start-up and commissioning are carried out in
cold weather.
3.7 Electrical connections - Preparation
Ensure the incoming power supply and the
distribution board are suitably rated.
Ensure that the regulations specified by the
local electricity supplier have been adhered to.
The supply cable must be suitable for the
installation location and sized to meet the
requirements of national wiring regulations for
current carrying capacity, disconnection time
and voltage drop; a minimum cross sectional
area of 6mm² steel wire armoured (SWA) cable
is recommended.
The required controller cable is a shielded
MODBUS cable RS485, such as a 4 core 1mm²
24 AWG (Nominal impedance 120Ω) Foil and
Braid, which can be purchased from Dimplex as
an accessory.
The user interface can be used as the
temperature thermostat in zone 1. The location
of the UI/zone 1 should be discussed before
installation with the end user. For multiple
zones, mechanical thermostats or NTC10
Comentários a estes Manuais