Connecting the Cooling
System
First, unwind the refrigerant pipes carefully to their
full length. The pipes may not have more than 3
bends in succession and a total of 12 bends over
their entire length.
The number of bends should be kept to a
minimum.
The radius of the bends must be at least 3.5 times
the external diameter. If necessary, a suitable
bending device should be used.
Connecting the refrigerant pipes:
See the section “Pre-filled refrigerant pipes KMSL”
for this.
Lay the suction and pressure pipes between the
indoor and outdoor unit. We recommend laying
the thicker suction pipes first, as the thinner
pressure pipes are more easily fitted in.
Excess piping should be wound up at a
downward angle to the outdoor unit in order to
avoid residues of refrigerant oil.
Remove the dust caps and dust plugs from the
two halves of the coupling.
The thread of the coupling and the seals should
be cleaned with a clean cloth to avoid trapping
dust and moisture in the system.
The membranes of the coupling and the rubber
seals of the male halves of the couplings should
be moistened with a few drops of refrigerant oil.
The matching halves of the couplings should be
screwed together by hand until the thread is well
engaged (or until the inner halves of the coupling
membrane meet – turning then becomes much
more difficult) and then tightened using a spanner
(see Torques for refrigerant pipe couplings). A
hissing noise during joining is normal.
Caution! When torque is applied, the two halves
of the coupling should always be held firm with
spanners.
Screw locks should then be applied to stop the
connection loosening unintentionally through
vibration.
After joining, the coupling connections must not
be opened (Refrigerant could escape! Repairs
must be carried out by an authorised after-sales
service only).
Torques for refrigerant pipe couplings
The necessary torques for the secure (leak-proof)
connection of the refrigerant pipe couplings are
given below:
Split pipes with refrigerant couplings with 3/8“ and
1/4" UNF threads (spanner values SW 19 und SW
21) 15 – 20 Nm.
Split pipes with refrigerant couplings with 5/8“ and
1/2" UNF threads (spanner values SW 27 und SW
34) 47 – 54 Nm.
All refrigerant pipes and connections must be
tested for leaks before first use (e.g. using a leak
search spray).
wrong
right