Publication 20L-TD001A 17
Frame 2 Power Terminal Locations
Frame 2 Power Terminal Specifications
Item Name Description
Recommended Tightening
Torque (+10%)
Terminal
Bolt Size
(1)
(1)
Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.
➊
Input Power Bus Bar
(2)
R/L1, S/L2, T/L3
(2)
These connections are bus bar type terminations and require the use of lug connectors.
Input power 40 N•m (354 lb•in) M8
➋
Output Power Bus Bar
(2)
U/T1, V/T2, W/T3
Motor connections 40 N•m (354 lb•in) M8
➌
PE, Motor Ground Bus Bar
(2)
Terminating point for wiring shields and grounds 40 N•m (354 lb•in) M8
➍
DC Bus Test Point Socket
(3)
(2 Terminals; DC+, DC-)
(3)
Use only to verify that DC bus capacitors are discharged before servicing the Power Module. No other external use is permitted.
4 mm socket for DC bus voltage measurement only — —
AA
Section A-A
W/T3
DC+
Testpoint
DC-
Testpoint
V/T2
U/T1
➋
T/L3S/L2R/L1
➊
➌
➍