PowerFlex 700L Technical Data
Publication 20L-TD001A 37
Standard Drive Specifications
The following specifications, unless otherwise noted, pertain to PowerFlex 700L drives equipped with 700 Vector Control
or 700S Phase II Control.
Category
Specification
Frame 2 Frame 3A/3B
Agency
Certification
Listed to UL508C and CAN/CSA-C2.2 No. 14-05. UL Listing for Frame 2 is applicable up to 480V AC. UL Listing for Frame 3A and 3B is
applicable up to 600V AC.
Marked for all applicable European Directives
(1)
EMC Directive (89/336/EEC)
EN 61800-3 Adjustable Speed electrical power drive systems
Low Voltage Directive (73/23/EEC)
EN 50178 Electronic Equipment for use in Power Installations
(1)
Applied noise impulses may be counted in addition to the standard pulse train causing erroneously high [Pulse Freq] readings.
Certified to AS/NZS, 1997 Group 1, Class A.
These drives are also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
CMAA Specification #70 (Crane Manufacturers of America Association)
Category
Specification
Frame 2 Frame 3A/3B
Protection 400V 480V 400V 480V 600V 690V
AC Input Overvoltage Trip: 528V AC 528V AC 528V AC 528V AC 760V AC 760V AC
AC Input Undervoltage Trip: 340V AC 340V AC 340V AC 340V AC 340V AC 340V AC
Bus Overvoltage Trip: 815V DC 815V DC 815V DC 815V DC 1168V DC 1168V DC
Bus Undervoltage Shutoff/Fault: 300V DC 300V DC 300V DC 300V DC 300V DC 300V DC
Nominal Bus Voltage: 600V DC 700V DC 600V DC 700V DC 900V DC 1000V DC
Heat Sink Thermistor: Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
200% of rated current (typical)
220-300% of rated current (dependent on drive rating)
Line Transients: Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity: Showering arc transients up to 1500V peak
Logic Control Ride-Thru
Vector Control: 0.5 seconds minimum, 2 seconds typical
700S Phase II Control: 0.25 seconds, drive not running
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output
Environment Altitude: 1000 m (3280 ft.) at rated current. See Derating Guidelines
on page 40 for operation above 1000 m (3280 ft.).
Maximum Surrounding Air
Temperature w/o Derating:
IP20, NEMA/UL Type 1: 0 to 50°C (32 to 122°F) 0 to 40°C (32 to 104°F)
Storage Temperature
(all constructions): –40 to 85°C (–40 to 185°F)
Atmosphere: Important: Drive must
not be installed in an area where the ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Relative Humidity: 5 to 95% non-condensing
Shock: 10G peak for 11 milliseconds duration (± 1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak, 5.5 Hz