Dimplex DC12 Manual de Serviço Página 38

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 37
PowerFlex 700L Technical Data
38 Publication 20L-TD001A
Electrical Voltage Tolerance
Vector Control: For full power and operating range, see the PowerFlex 700 Adjustable Frequency AC Drive — Series B User Manual
(publication 20B-UM002), Appendix C.
700S Phase II Control: For full power and operating range, see the PowerFlex 700S High Performance AC Drive — Phase II Control User
Manual (publication 20D-UM006), Appendix C.
Input Frequency Tolerance: 27-93 Hz.
Input Phases: Three-phase input provides full rating for all drives.
Displacement Power Factor: 0.98 across entire speed range.
Efficiency: 96.2% at rated amps, nominal line volts. 97.5% at rated amps, nominal line volts.
Maximum Short Circuit Current
Rating: To match specified circuit breaker capability,
200,000 Amps
Actual Short Circuit Rating: Determined by AIC rating of installed circuit breaker.
Motor Lead Lengths: 76 meters (250 feet) total
Control Method: Sine coded PWM with programmable carrier frequency.
Carrier Frequency: 2, 4, or 8 kHz. Drive rating based on 4 kHz.
See Derating Guidelines
on page 40 for more information.
2 or 4 kHz. Drive rating based on 4 kHz.
Output Voltage Range: 0 to rated motor voltage
Output Frequency Range
Vector Control: 0 to 420 Hz
700S Phase II Control: 0 to 350 Hz
Frequency Accuracy (Vector
Control only)
Digital Input:
Analog Input:
Within ± 0.01% of set output frequency.
Within ± 0.4% of maximum output frequency
Frequency Control
(Vector Control only):
Speed Regulation - w/Slip Compensation (Volts per Hertz Mode)
0.5% of base speed across 40:1 speed range
40:1 operating range
10 rad/sec bandwidth
Speed Regulation - w/Slip Compensation (Sensorless Vector Mode)
0.5% of base speed across 80:1 speed range
80:1 operating range
20 rad/sec bandwidth
Speed Control
Vector Control: Speed Regulation - without feedback (Vector Control Mode)
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Regulation - with feedback (Vector Control Mode)
0.001% of base speed across 120:1 speed range
1000:1 operating range
250 rad/sec bandwidth
700S Phase II Control: Speed Regulation - without feedback
0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth
Speed Regulation - with feedback
0.001% of base speed across 120:1 speed range
1000:1 operating range
740 rad/sec bandwidth
Torque Regulation
Vector Control: Torque regulation without Feedback; ± 5%, 600 rad/sec bandwidth
Torque regulation with Feedback; ± 2%, 2500 rad/sec bandwidth
700S Phase II Control: Torque regulation without Feedback; ± 10%, 600 rad/sec bandwidth
Torque regulation with Feedback; ± 5%, 4400 rad/sec bandwidth
Selectable Motor Control
Vector Control: Sensorless Vector with full tuning. Standard V/Hz with full custom capability and Vector Control with Force
Technology (with and without feedback).
700S Phase II Control: Vector Control with Force Technology (with and without feedback), V/Hz Control, and permanent magnet motor
control.
Category
Specification