PowerFlex 700L Technical Data
40 Publication 20L-TD001A
Derating Guidelines
Altitude
Above 1000 m (3280 ft.), derate the output current by 1% for every 100 additional meters (328 additional feet). This is
applicable to filters and power modules. PowerFlex 700L 600/690V drives should not be used above 2000 m (6562 ft.)
due to voltage spacing requirements.
Ambient
Frame 2 drives have a maximum ambient of 50°C (122°F). Frame 3A and 3B drives have a maximum ambient of 40°C
(104°F). PowerFlex 700L drives cannot be derated to operate at higher ambients.
Carrier Frequency
For Frame 2 drives, refer to the carrier frequency derating table below. PowerFlex 700L Frame 3A and 3B drives cannot
be run above 4 kHz.
Watts Loss (@ Rated Load, Speed, and PWM Carrier Frequency)
Frame
Size Voltage
PWM
Freq.
Watts Loss
Filter Section Power Section Complete Drive
Into Air Into Air Into Liquid Total Total Air Total Liquid
2 400V 4 kHz
Not Applicable 1500 7900
480V 4 kHz
Not Applicable 1500 7900
3A 400V 4 kHz 4000 1000 10,500 11,500 5000 10,500
480V 4 kHz 4000 1000 11,500 12,500 5000 11,500
600V 4 kHz 4000 1200 10,500 11,700 5200 10,500
690V 4 kHz 4000 1200 12,000 13,200 5200 12,000
3B
(1)
(1)
Frame 3B power section consists of two (2) power modules. Each module dissipates half (½) of the watts shown in this table.
400V 4 kHz 7800 2000 21,000 23,000 9800 21,000
480V 4 kHz 7800 2000 23,000 25,000 9800 23,000
600V 4 kHz 7800 2400 21,000 23,400 10,200 21,000
690V 4 kHz 7800 2400 24,000 26,400 10,200 24,000
2
0
4
6
8
360
Output
(Amps)
293 Amps
(80%)
Carrier Frequency (kHz)
PowerFlex 700L Frame 2 Drive
Carrier Frequency Derating