PowerFlex 700L Technical Data
Publication 20L-TD001A 41
Cooling Loop Options
This section provides information about the various types of cooling loops.
Liquid-to-Liquid Heat Exchanger
The liquid-to-liquid heat exchanger utilizes a heat transfer plate to transfer heat from one liquid to another. This method
requires a stable water supply from the user.
The drawing below shows a cooling loop diagram for a typical liquid-to-liquid heat exchanger.
The main components of the liquid-to-liquid heat exchanger cooling loop include:
Part Description
Strainer Filters particles from the supply water.
Control Valve Controls the supply loop water flow.
Heat Exchanger Plate Transfers heat from the drive loop to the supply loop.
Ambient Sensor Senses the ambient temperature used for the dew point control.
Drive Coolant Temperature Sensor Senses the drive coolant temperature used for the dew point control.
Drive Coolant Flow Switch Measures the drive coolant flow rate.
Level Switch Senses the level of coolant in the reservoir.
Reservoir Stores drive coolant.
Pump and Motor Circulates drive coolant.
PowerFlex 700L
Drive
Inlet
Drive
Outlet
Hose Kit
= hose or pipe connection
To Facility Wate
To
Drive
Inlet
From
Drive
Outlet
Return
To
Supply
In
From
Supply
Liquid-to-Liquid
Heat Exchanger
Customer
Supplied Piping
Flow
Indicator
Ambient Sensor
Heat Exchanger
Pump
Reservoir
Drive
IN
OUT
IN
OUT
OUT
IN
Drive Coolant Temp.
Control
Valve
Strainer
Supply
Process
Water
Flow Switch
Level Switch
TE
TE FS
LS